Multiple Detectors on the same Zone
Door Contacts
When connecting morethan onedoor contactto
azone, the alarm contactsmustbe connected in
series. The switch inside the contact is connected
between the two plated screws (shown in white in
the above figure).
Passive Infra-Red
Whenconnectingmore than one PIRtoazone it is
recommended that you use "Latching" type PIRs.
The latch terminal on the PIR is connected to the
[RST-] output which must then be programmed as
SW 12V.
Auxiliary Tamper
The tamper wires for each detector must be
connected in series using a terminal strip or similar
and then connect to the AUX TAMPER terminals.
9
TS400/TS410 Installation Instructions System Installation
AUX
TAMPER
ZONE
To tamper loop
for other zones
Flush ContactFlush Contact
AUX
TAMPER
ZONE
Surface ContactSurface Contact
Connecting several
flush contacts per zone
Connecting several
suface contacts per zone
AUX
TAMPER
AUX
12V
Connecting several
PIRs per zone
Program [RST-] as
SW 12V
PIR
0V
+12V
ALARM
TAMPER
LATCH
ZONE
+
-
PIR
0V
+12V
ALARM
TAMPER
LATCH
RST -
To tamper loop
for other zones
To tamper loop
for other zones
Figure 4 Connecting Multiple Detectors per Zone
AUX
TAMPE
R
Terminal Strip (Not Supplied)
Tamper Loop
Tamper Loop
Tamper Loop
Tamper Loop
Figure 5 Auxiliary Tamper Connection