TS790+ & TS900+ Intruder Alarm Control Panels Installation and Programming Manual
System Installation TS790+ & TS900+ Installation Manual Control Panel Installation Proceed as follows: 1. Open the control panel by removing the
TS790+ & TS900+ Installation Manual System Installation Control Panel PCB Layout Figure 6. TS790+ & TS900+ Main PCB
System Installation TS790+ & TS900+ Installation Manual Connection Terminals & Indicators The main PCB has the following “Jumper Plugs” (JP)
TS790+ & TS900+ Installation Manual System Installation Mains Connection The mains supply is connected to a 3 way "Euro Type" fused ter
System Installation TS790+ & TS900+ Installation Manual If this jumper link is set to the “enabled” position, the red (ü) LED on the keypad will
TS790+ & TS900+ Installation Manual System Installation as normal. When the link is set to the enabled position the sounder is only enabled when
System Installation TS790+ & TS900+ Installation Manual A B F GA B F GA B C D EAUX 12V500mAREMOTE500mAAUX 12VAUX 12V SPEAKEROUTPUT MODULEREMOTE Z
TS790+ & TS900+ Installation Manual System Installation Installing an XNode 1. Separate the cover and base by using a screwdriver to push 2 of t
System Installation TS790+ & TS900+ Installation Manual TS700 LEC Installation The TS700 LEC (Local Expansion Card) is connected to the “Remote N
TS790+ & TS900+ Installation Manual System Installation Figure 14. Double Pole Wiring End Of Line The EOL method requires the following: The det
© Cooper Security Limited 2003 Every effort has been made to ensure that the contents of this book are correct, errors and omissions escepted. Howeve
System Installation TS790+ & TS900+ Installation Manual Figure 16. External Sounder Connections Installing an External Sounder from a XNode The
TS790+ & TS900+ Installation Manual System Installation Auxiliary Tamper These two terminals provide tamper protection to auxiliary devices such
System Installation TS790+ & TS900+ Installation Manual Figure 20. DC54/DC58 Connections Plug-on digi-Modem Installation A plug-on digi-modem DC
TS790+ & TS900+ Installation Manual System Installation Using the DATAC / RS232 Printer 1. Plug the DCI/MPA on to the PRINTER plug (JP1) on the
System Installation TS790+ & TS900+ Installation Manual Programmable Outputs The TS790+/900+ has many programmable outputs which can be used to d
TS790+ & TS900+ Installation Manual System Installation Installing a Monitored Power Supply The TS790+/TS900+ can be configured to monitor the 51
System Installation TS790+ & TS900+ Installation Manual Power-Up Checks When the initial power-up checks have been completed, check the following
TS790+ & TS900+ Installation Manual System Installation Section Option Default 11 Service Time 000 weeks 12 Payment Time 000 weeks 13 Part Set
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual Engineer’s Menu 1 Introduction Engineers menu 1 is the first of three engineers menus, whic
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 Panel Outputs [1.1] Outputs 1 - 4 on the control panel and remote keypad outputs 5 - 8 can
Contents Overview ... 1 Introduction ... 1 System Architecture.
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual No/Type Description 008 System Set Activates when any ward is set and deactivates when the
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 No/Type Description 046 Service Call Activates when the system is on-line with a remote PC
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual No/Type Description 200 - 255 Circuit Alarms Active when a circuit causes an alarm, for ci
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 A PSU-Battery This circuit may be connected to the 519XB power supply via the 519 FM PCB to
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual 8 Chime Circuits with this attribute will cause the internal sounders and remote keypad sou
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 activated and the “2nd Entry. . .” timer is started. This timer has a working range of 000-
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual when the user enters their passcode the exit timer starts and the system attempts to set, o
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 28 Abort Delay This timer sets the period in which the alarm signal may be aborted followin
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual Setting Modes Flowchart Do System Print [1.7] If a printer is connected to the control pan
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 02 Fire Signals all When programmed as “Yes” fire alarm activations are signalled to the AR
Alter 24Hr Group [2.6] ... 41 Print System Log [2.7]... 41 Configure Wards [2.8]...
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual 17 Loud Chime Tones When programmed as “Yes” the chime tones are always at full volume. Whe
TS790+ & TS900+ Installation Manual Engineer’s Menu 1 for an intruder alarm as normal. If a subsequent zone is triggered within the same set peri
Engineer’s Menu 1 TS790+ & TS900+ Installation Manual User Menu 1 Flowchart View Location Text (LCD Only) [1.B] This option allows the engin
TS790+ & TS900+ Installation Manual Engineer’s Menu 2 Engineers Menu 2 Introduction Engineer’s menu 2 is selected by pressing the [ENT] key whils
Engineer’s Menu 2 TS790+ & TS900+ Installation Manual View Circuits [2.1] Each detection circuit may be viewed to ascertain its status. The circ
TS790+ & TS900+ Installation Manual Engineer’s Menu 2 Chime Circuits [2.5] This option allows an alternative method of programming circuits as “
Engineer’s Menu 2 TS790+ & TS900+ Installation Manual Configure Wards Flowchart View System Log [2.9] The engineer can use this option to view t
TS790+ & TS900+ Installation Manual Engineer’s Menu 2 Log Event Codes LCD Starburst LED Description ACTION ALARM ALM SENT AA Bell output activ
Engineer’s Menu 2 TS790+ & TS900+ Installation Manual LCD Starburst LED Description SYSTEM RE-ARMED RE-ARMED rA System re-armed all healthy ci
TS790+ & TS900+ Installation Manual Engineer’s Menu 3 Engineer’s Menu 3 Introduction Engineers menu 3 is selected by pressing the [ENT] whilst En
TS790+ & TS900+ Installation Manual Oveview Overview Introduction The TS790+ and TS900+ alarm control units are designed for medium to large inst
Engineer’s Menu 3 TS790+ & TS900+ Installation Manual Time Switches [3.1] The TS790+/TS900+ has three programmable time switches. Each time swit
TS790+ & TS900+ Installation Manual Engineer’s Menu 3 Part Set Groups [3.2] This option allows the engineer to define how the three part set but
Engineer’s Menu 3 TS790+ & TS900+ Installation Manual Engineers Name (LCD Only) [3.4] This option allows the engineer to assign a name (7 charac
TS790+ & TS900+ Installation Manual Engineer’s Menu 3 Location Text This option allows the engineer to program a 32 character location message. W
Engineer’s Menu 3 TS790+ & TS900+ Installation Manual Voltage When this test option is selected the battery charging voltage at the control panel
TS790+ & TS900+ Installation Manual Engineer’s Menu 3 Custom Outputs A & B [3.A/B] These options allows the engineer to program both custom
Engineer’s Menu 3 TS790+ & TS900+ Installation Manual Modem Options (LCD Only) [3.C] This option allows the engineer to access the following mod
TS790+ & TS900+ Installation Manual Engineer’s Menu 3 Program Digi Flowchart
Engineer’s Menu 3 TS790+ & TS900+ Installation Manual Reset Digicom When the system is powered up, the control panel logs-on the device that is c
TS790+ & TS900+ Installation Manual Appendices Appendices Contact ID Extended Reporting Contact ID extended reporting is a new format which when
Overview TS790+ & TS900+ Installation Manual Remote Keypads Up to 4 remote keypads can be connected to the control panel. Each remote keypad has
Appendices TS790+ & TS900+ Installation Manual Figure 26. A Typical 3 Bedroom House Domestic Part-Set Application Example
TS790+ & TS900+ Installation Manual Appendices The TS790+/900+ is very flexible in the way that the system can be part-set. The system may be par
Appendices TS790+ & TS900+ Installation Manual Defining Part-Set buttons to Arm a Ward(s) This method of defining the part set groups requires yo
TS790+ & TS900+ Installation Manual Appendices Figure 27. Commercial Premises
Appendices TS790+ & TS900+ Installation Manual Commercial Part-Set Application This application example shows how to use the "Code Set Group
TS790+ & TS900+ Installation Manual Appendices 1. Program the Detection Circuit as a “Key Switch” and set the attributes as “F * * * |* A * *”.
Appendices TS790+ & TS900+ Installation Manual Figure 30. Alarm Abort & Sequential Confirmation 1. If a plug-on digicom is being used progr
TS790+ & TS900+ Installation Manual Appendices Users 02-31 may be programmed as "Reset Only". This user type allows 24hr alarms to be r
Appendices TS790+ & TS900+ Installation Manual Quick Reference Engineers Menus Engineers Menu 1 key Options Page 1 Program Panel Outputs 1 = Pan
TS790+ & TS900+ Installation Manual Appendices Quick Reference Engineers Menus Engineers Menu 2 key Options Page 1 View Circuits A = Scroll Nex
TS790+ & TS900+ Installation Manual Overview Specifications General Zones TS790+ - 10 to 16 TS900+ - 10 to 56 Expansion 2 zone LECs and/or K
Appendices TS790+ & TS900+ Installation Manual Quick Reference Engineers Menus Programmable Output Types No. Output Type 000 Bell On 001 Stro
System Installation TS790+ & TS900+ Installation Manual System Installation Cable Routing When installing cables, the following should be noted:
TS790+ & TS900+ Installation Manual System Installation Remote Network Wiring Devices on the “Remote Network” require a 6 core cable for intercon