System Timers
The system timers are as follows:
00 Test Call At
This timer controls the hour at which the control
unit sends a timed test call. For example, if the
timer is set at 003 (default) then the control unit
sends a test call at 03:00 am. If the timer is set
to 014 then the control unit sends the test call
at 02:00 pm.
01 No of Re-Arms
At the end of the bell duration time the system
re-arms all circuits that are healthy. Circuits that
are still in an alarm are isolated until they
change to a healthy condition. This counter
controls the number of times that a "circuit" will
re-arm before it is locked out of the system. This
counter has a working range of 000-199.
02 Settle Time
When setting the system by “Final Exit” or “Exit
Terminator”, detectors that are on the exit route
sometimes take 3-4 seconds to settle after
activation. The delay programmed in this timer
is used to allow these detectors to settle before
the system or area is set. This timer has a
working range of 000-199 seconds.
03 Part Set Comms Delay
When the system is part-set the
communication of an alarm signal to the
central station can be delayed by the value
set in this timer. If the timer is set to 199 the
part-set communications are disabled. This
timer has a working range of 000-199 seconds.
04 Exit Time
This timer sets the delay between the user
initiating the exit procedure and the system (or
area) actually setting. If during the exit time an
“Exit Terminator” circuit is activated the exit
time is cancelled and the system sets
immediately. This timer has a working range of
000-199 seconds.
05 Entry Time
When the system is set or part-set, and the entry
procedure is initiated, the entry timer starts to
count down. If a valid user passcode has not
been entered when the timer reaches zero,
the internal sounders are activated and the
“2nd Entry. . .” timer is started. This timer has a
working range of 000-199 seconds.
06 Bell Duration
This controls the duration of the external
bell/sounder. If the timer is set to 199 the bell
output is continuous. This timer has a working
range of 000-199 minutes.
27
TS790 & TS900 Installation Manual Engineer’s Menu 1
Program circuits
Enter CCT No.>--
CCT 04 NIGHT
CCT 04 F.EXIT
>********
CCT 04 F.EXIT
>*******C
Enter circuit type:
= Not Used
=Night
= 24hr
= PA Silent
Circuit No.
Attributes
Circuit Type
4
0
1
2
3
ENT
Enter circuit No.
e.g. 04
= Final Exit
= Exit Terminator
=KeyPoint
= PSU-Battery
7
8
9
A
ENT
e.g. 7 for Final Exit
Select attributes:
= ccessA
= KnockD
=estT
1
2
3
=esetR
= laggedF
=ntryE
5
6
7
ENT
e.g. 6 for chime
= PA Audible
4
=PSU-Fuse
B
=Fire
5
= PSU-Power
C
= Auxiliary
6
=mitO4 =himeC8
Engineers menu 1
Select Options :-
StarburstLCD
LED
E1 -
ENGR 1 -
CT.--
CCT NO.--
NITE
NIGHT
04
FE
04
F.EXIT
04
FE
CHI
04
F.EXIT
CHIME
Program Circuits Flowchart